Model | ENC-ARW2200L | ENC-ARW2900L |
Type | Water lateral-mount type |
Cooling scheme | Water cooling (Condensor) |
Cooling capacity (W) | 2000/2200(50/60Hz) | 2600/2900(50/60Hz) |
Power supply (50/60Hz) | 3 phase 200VAC±10% |
Current consumption (A)(MAX) | 2.70/2.52 | 3.4/3.8 |
Starting current (A) | 9.0/8.6 | 14.0/12.2 |
Power consumption (W)(MAX) | 590/670 | 940/1160 |
Required amount of cooling water (L/min) | 7.2/7.9 or higher | 9.7/11.1 or higher |
Required pressure of cooling water (MPa) | 0.03 to 0.98 |
Required pressure of cooling water (MPa) | Required pressure of cooling water (MPa) |
Diameter of cooling water | INLET : Rc1/2(15A) OUTLET : Rc1/2(15A) |
Allowable ambient humidity (%) | 10 to 80 (No condensation) |
Operation control scheme | Microcomputer-based automatic control |
Refrigerant | R-407c (A kind of freon that is not prohibited) |
Temperature setting range (ºC) | 25 to 45 |
Number of fans | 2 |
Noise immunity | 2 |
Noise immunity | Level 2 in the fast transient/Burst immunity test |
Noise (dB) | 60/60 |
Vibration resistance | Vibration frequency : 5Hz ; a double amplitude of 20mm |
Enclosure rating | Corresponding to IP54 (Internal circulation course) |
Paint color | Munsell 5Y7/1 Equivalent color of light beige |
Outer dimensions (mm) | H:1000×W:450×D:230 |
Weight(kg) | 42 | 49 |