Cabinet & Component

APISTE Server Rack Cooling Unit
APISTE Server Rack Cooling Unit – Rack-mount Type […]

APISTE Server Rack Cooling Unit – Rack-mount Type

ITC-M1700AS

ModelITC-M1700AS(N)
TypeRack-mount Type
Cooling schemeCompressor
Cooling capacity (W)1500/1700 (50/60Hz)
Power supply (50/60Hz)1phase 100VAC±10%
Current consumption (A)(MAX)6.8/7.6
Power consumption (W)(MAX)610/725
Allowable ambient temperature (ºC)5 to 40 (25 to 40 when cooled)
Allowable ambient humidity (%)70 or less
RefrigerantR-404A
Number of fans5
OutputERR: All 21 items are output with OR circuit.
(AC250V 1A)
DisplayLED Temperature/Error Run
Noise immunityLevel 4 in the fast transient/Burst immunity test
Noise (dB)58 or less
Paint colorA color corresponding to AN-30 dark gray
Front panel: Silver
Air volume(m3/min)13/10
Outer dimensions(mm)Main UnitH176(4U)×W432×D1080
ControllerH44 (1U)×W420×D150
Weight(kg)45.2

APISTE Server Rack Cooling Unit – Standalone Type

ITC-AR1300S

ModelITC-AR1300S
TypeStand alone type
Cooling schemeCompressor
Cooling capacity (W)1100/1300 (50/60Hz)
Power supply (50/60Hz)1phase 100VAC±10%
Current consumption (A)(MAX)8.3/9.2
Starting current (A)22.3/20.5
Power consumption (W)(MAX)750/890
Allowable ambient temperature (ºC)20 to 40
Allowable ambient humidity (%)40 to 70 (No condensation)
RefrigerantR-407c
Temperature control range (ºC)25 to 45
Number of fans2
OutputError output
DisplayLED Temperature/Error Run/Drain Alarm(RED)
Noise immunityLevel 4 in the fast transient/Burst immunity test
Noise (dB)Approx. 50/55
Paint colorA color corresponding to AN-30 dark gray
Outer dimensions(mm)H900×W400×D300
Weight(kg)42

ITC-AR1900S

ModelITC-AR1900S
TypeStand alone type
Cooling schemeCompressor
Cooling capacity (W)1800/1900 (50/60Hz)
Power supply (50/60Hz)1phase 100VAC±10%
Current consumption (A)(MAX)7.7/8.0
Starting current (A)22.3/20.5
Power consumption (W)(MAX)680/760
Allowable ambient temperature (ºC)20 to 40
Allowable ambient humidity (%)40 to 70 (No condensation)
RefrigerantR-407c
Temperature control range (ºC)25 to 45
Number of fans3
OutputError output
DisplayLED Temperature/Error Run/Drain Alarm(RED)
Noise immunityLevel 4 in the fast transient/Burst immunity test
Noise (dB)Approx. 60/55
Paint colorA color corresponding to AN-30 dark gray
Air volume(m3/min)13/10
Outer dimensions(mm)H1400×W550×D400
Weight(kg)70

ITC-1810S

ModelITC-1810S
TypeStand alone type
Cooling schemeCompressor
Cooling capacity (W)1500/1800(50/60Hz)
Power supply (50/60Hz)1phase 100VAC±10%
Current consumption (A)(MAX)9.0/9.0
Starting current (A)22.3/20.5
Power consumption (W)(MAX)760/850
Allowable ambient temperature (ºC)25 to 40
Allowable ambient humidity (%)10 to 85 (No condensation)
RefrigerantR-407c (A kind of freon that is not prohibited)
Temperature control range (ºC)25 to 45
Number of fans5
OutputError output
DisplayLED Temperature/Error Run
Noise immunityLevel 2 in the fast transient/Burst immunity test
Noise (dB)55/55
Paint colorA color corresponding to AN-30 dark gray
Air volume(m3/min)5.0/5.8
Outer dimensions(mm)H:1100×W:500×D:250
Weight(kg)51

APISTE Server Rack Cooling Unit – Ceiling-mount Type

ITC-A1600EX

ModelITC-A1600EX
TypeTop-mount type for server rack
Cooling schemeCompressor
Cooling capacity (W)1450/1600(50/60Hz)
Power supply (50/60Hz)1phase 100VAC±10%
Current consumption (A)(MAX)12.0/11.5
Starting current (A)31.6/29.4
Power consumption (W)(MAX)1100/1150
Allowable ambient temperature (ºC)20 to 40
Allowable ambient humidity (%)40 to 70 (No condensation)
RefrigerantHFC-134a (A kind of freon that is not prohibited.)
Temperature control range (ºC)25 to 45
Number of fans4
OutputOutput of operation & alarm(250V 2A)
DisplayLED Temperature/Error Run
Noise immunityLevel 4 in the fast transient/Burst immunity test
Noise (dB)62/59
Paint colorA color corresponding to AN-30 dark gray
Air volume(m3/min)12.4/14.6
Outer dimensions(mm)H:300×W:605×D:800
Weight(kg)63

APISTE Server Rack Cooling Unit – Fan Unit for Server Rack

ITC-DFU-011

ModelITC-DFU-011
TypeFan unit
Airflow capacity(m3/min)9.6/11.4
Power supply (50/60Hz)1phase 100VAC±10%
Current consumption (A)(MAX)0.55/0.46
Power consumption (W)(MAX)36/31
Noise (dB)Approx. 56/58
Outer dimensions(mm)H77.8×W486×D350
Weight(kg)5.3

ITC-DFU-2U/3U

ModelITC-DFU-2UITC-DFU-3U
TypeFan unit
Airflow capacity(m3/min)6.0/6.24.5/4.6
Power supply (50/60Hz)1phase 100VAC±10%
Current consumption (A)(MAX)0.25/0.330.34/0.38
Power consumption (W)(MAX)25/3233/38
Noise (dB)Approx. 56/58Approx. 47/48
Outer dimensions(mm)H95×W443×D700H32×W433×D700
Weight(kg)11