Model | ENC-A510HD | ENC-A520HD |
Type | Outdoors lateral-mount type | |
Cooling scheme | Compressor | |
Cooling capacity (W) | 300/380(50/60Hz) | |
Power supply (50/60Hz) | 1 phase 100VAC±10% | 1 phase 200VAC±10% |
Current consumption (A)(MAX) | 3.9/3.8 | 2.0/1.7 |
Starting current (A) | 7.4/7.7 | 4.0/4.2 |
Power consumption (W)(MAX) | 330/370 | 330/320 |
Allowable ambient temperature (ºC) | 0 to 50 | |
Allowable ambient humidity (%) | 10 to 85 (No condensation) | |
Operation control scheme | Microcomputer-based automatic control | |
Refrigerant | R-134a (A kind of freon that is not prohibited) | |
Temperature setting range (ºC) | 25 to 45 | |
Number of fans | 1 | |
Outer dimensions (mm) | H:300×W:115×D:530 | |
Weight(kg) | 15 |
Model | ENC-AR510HD | ENC-AR520HD |
Type | Outdoors lateral-mount type | |
Cooling scheme | Compressor | |
Cooling capacity (W) | 450/550(50/60Hz) | |
Power supply (50/60Hz) | 1 phase 100VAC±10% | 1 phase 200VAC±10% |
Current consumption (A)(MAX) | 3.9/4.2 | 2.1/1.9 |
Starting current (A) | 7.4/7.7 | 4.9/4.4 |
Power consumption (W)(MAX) | 365/410 | 365/360 |
Allowable ambient temperature (ºC) | -5 to 50 | |
Allowable ambient humidity (%) | 10 to 85 (No condensation) | |
Operation control scheme | Microcomputer-based automatic control | |
Refrigerant | R-134a (A kind of freon that is not prohibited) | |
Temperature setting range (ºC) | 25 to 45 | |
Number of fans | 2 | |
Outer dimensions (mm) | H:450×W:350×D:200 | |
Weight(kg) | 17 |
Model | ENC-A1010HD | ENC-A1020HD |
Type | Outdoors lateral-mount type | |
Cooling scheme | Compressor | |
Cooling capacity (W) | 900/1000 (50/60Hz) | |
Power supply (50/60Hz) | 1 phase 100VAC±10% | 1 phase 200VAC±10% |
Current consumption (A)(MAX) | 6.5/6.3 | 3.1/3.0 |
Starting current (A) | 15.6/14.7 | 7.5/7.1 |
Power consumption (W)(MAX) | 595/615 | 570/590 |
Allowable ambient temperature (ºC) | -5 to 50 | |
Allowable ambient humidity (%) | 10 to 85 (No condensation) | |
Operation control scheme | Microcomputer-based automatic control | |
Refrigerant | R-134a | |
Temperature setting range (ºC) | 25 to 45 | |
Number of fans | 2 | |
Output | Output of operation & alarm(250V 2A) | |
Display | LED Temperature/Error Run | |
Noise immunity | Level 4 in the fast transient/Burst immunity test | |
Noise (dB) | Approx. 64/66 | |
Vibration resistance | Vibration frequency : 5Hz ; a double amplitude of 20mm | |
Outer dimensions (mm) | H730×W300×D280 | |
Weight(kg) | 26 |
Model | ENC-AR1010HD | ENC-AR1020HD |
Type | Outdoors lateral-mount type | |
Cooling scheme | Compressor | |
Cooling capacity (W) | 900/1000 (50/60Hz) | |
Power supply (50/60Hz) | 1 phase 100VAC±10% | 1 phase 200VAC±10% |
Current consumption (A)(MAX) | 6.5/6.3 | 3.1/3.0 |
Starting current (A) | 15.6/14.7 | 7.5/7.1 |
Power consumption (W)(MAX) | 595/615 | 570/590 |
Allowable ambient temperature (ºC) | -5 to 50 | |
Allowable ambient humidity (%) | 10 to 85 (No condensation) | |
Operation control scheme | Microcomputer-based automatic control | |
Refrigerant | R-134a | |
Temperature setting range (ºC) | 25 to 45 | |
Number of fans | 2 | |
Output | Output of operation & alarm(250V 2A) | |
Display | LED Temperature/Error Run | |
Noise immunity | Level 4 in the fast transient/Burst immunity test | |
Noise (dB) | Approx. 64/66 | |
Vibration resistance | Vibration frequency : 5Hz ; a double amplitude of 20mm | |
Outer dimensions (mm) | H730×W300×D280 | |
Weight(kg) | 26 |
Model | ENC-A1610HD | ENC-A1620HD |
Type | Outdoors lateral-mount type | |
Cooling scheme | Compressor | |
Cooling capacity (W) | 1450/1600 (50/60Hz) | |
Power supply (50/60Hz) | 1 phase 100VAC±10% | 1 phase 200VAC±10% |
Current consumption (A)(MAX) | 8.5/8.8 | 4.3/4.5 |
Starting current (A) | 22.3/20.5 | 13/12 |
Power consumption (W)(MAX) | 740/830 | 780/840 |
Allowable ambient temperature (ºC) | -5 to 50 | |
Allowable ambient humidity (%) | 10 to 85 (No condensation) | |
Operation control scheme | Microcomputer-based automatic control | |
Refrigerant | R-407c (A kind of freon that is not prohibited) | |
Temperature setting range (ºC) | 25 to 45 | |
Number of fans | 4 | |
Outer dimensions (mm) | H:1000×W:400×D:260 | |
Weight(kg) | 42 |
Model | ENC-AR1610HD | ENC-AR1620HD |
Type | Outdoors lateral-mount type | |
Cooling scheme | Compressor | |
Cooling capacity (W) | 1450/1600 (50/60Hz) | |
Power supply (50/60Hz) | 1 phase 100VAC±10% | 1 phase 200VAC±10% |
Current consumption (A)(MAX) | 8.5/8.8 | 4.3/4.5 |
Starting current (A) | 22.3/20.5 | 13/12 |
Power consumption (W)(MAX) | 740/830 | 780/840 |
Allowable ambient temperature (ºC) | -5 to 55 | |
Allowable ambient humidity (%) | 10 to 85 (No condensation) | |
Operation control scheme | Microcomputer-based automatic control | |
Refrigerant | R-407c (A kind of freon that is not prohibited) | |
Temperature setting range (ºC) | 25 to 45 | |
Number of fans | 4 | |
Outer dimensions (mm) | H:1000×W:400×D:260 | |
Weight(kg) | 42 |
Model | ENC-A2900HD |
Type | Outdoors lateral-mount type |
Cooling scheme | Compressor |
Cooling capacity (W) | 2600/2900(50/60Hz) |
Power supply (50/60Hz) | 1 phase 200VAC±10% |
Current consumption (A)(MAX) | 9.3/9.4 |
Starting current (A) | 33/30 |
Power consumption (W)(MAX) | 1650/1850 |
Allowable ambient temperature (ºC) | -5 to 55 |
Allowable ambient humidity (%) | 10 to 85 (No condensation) |
Operation control scheme | Microcomputer-based automatic contorl |
Refrigerant | R-134a (A kind of freon that is not prohibited) |
Temperature setting range (ºC) | 25 to 45 |
Number of fans | 6 |
Outer dimensions (mm) | H:1380×W:450×D:295 |
Weight(kg) | 60 |
Model | ENC-AR2900HD |
Type | Outdoors lateral-mount type |
Cooling scheme | Compressor |
Cooling capacity (W) | 2600/2900(50/60Hz) |
Power supply (50/60Hz) | 1 phase 200VAC±10% |
Current consumption (A)(MAX) | 9.3/9.4 |
Starting current (A) | 33/30 |
Power consumption (W)(MAX) | 1650/1850 |
Allowable ambient temperature (ºC) | -5 to 55 |
Allowable ambient humidity (%) | 10 to 85 (No condensation) |
Operation control scheme | Microcomputer-based automatic contorl |
Refrigerant | R-134a (A kind of freon that is not prohibited) |
Temperature setting range (ºC) | 25 to 45 |
Number of fans | 6 |
Outer dimensions (mm) | H:1380×W:450×D:295 |
Weight(kg) | 60 |