Cabinet & Component

APISTE Panel Cooling Unit – Non-drain Lateral-mount Type
APISTE Panel Cooling Unit – Non-drain Lateral-mou […]

APISTE Panel Cooling Unit – Non-drain Lateral-mount Type

ENC-AR310LE/AR320LE

ModelENC-AR310LEENC-AR320LE
TypeNon-drain Lateral-mount type
Cooling schemeCompressor
Cooling capacity (W)280/300 (50/60Hz)
Power supply (50/60Hz)1 phase 100VAC±10%1 phase 200VAC±10%
Current consumption (A)(MAX)3.7/3.82.1/1.9
Starting current (A)7.4/7.74.0/4.2
Power consumption (W)(MAX)340/370360/355
Allowable ambient temperature (ºC)20 to 50
Allowable ambient humidity (%)10 to 85 (No condensation)
RefrigerantR-134a (A kind of freon that is not prohibited)
Temperature setting range (ºC)25 to 45
Number of fans2
OutputOutput of operation & alarm(250V 2A)
DisplayLED Temperature/Error RUN
Noise immunityLevel 4 in the fast transient/Burst immunity test
Noise (dB)Approx. 59/63
Vibration resistanceVibration frequency : 5Hz ; a double amplitude of 20mm
Paint colorMunsell 5Y7/1 Equivalent color of light beige
Outer dimensions (mm)H590×W200×D250
Weight(kg)18

ENC-AR510LE/AR520LE

ModelENC-AR510LEENC-AR520LE
TypeNon-drain Lateral-mount type
Cooling schemeCompressor
Cooling capacity (W)400/500 (50/60Hz)
Power supply (50/60Hz)1 phase 100VAC±10%1 phase 200VAC±10%
Current consumption (A)(MAX)3.6/3.71.9/1.6
Starting current (A)7.4/7.74.0/4.2
Power consumption (W)(MAX)320/360330/300
Allowable ambient temperature (ºC)20 to 50
Allowable ambient humidity (%)10 to 85 (No condensation)
RefrigerantR-134a (A kind of freon that is not prohibited)
Temperature setting range (ºC)25 to 45
Number of fans2
OutputOutput of operation & alarm(250V 2A)
DisplayLED Temperature/Error RUN
Noise immunityLevel 4 in the fast transient/Burst immunity test
Noise (dB)Approx. 63/67
Vibration resistanceVibration frequency : 5Hz ; a double amplitude of 20mm
Paint colorMunsell 5Y7/1 Equivalent color of light beige
Outer dimensions (mm)H500×W350×D230
Weight(kg)19

ENC-AR810LE/AR820LE

ModelENC-AR810LEENC-AR820LE
TypeNon-drain Lateral-mount type
Cooling schemeCompressor
Cooling capacity (W)700/800 (50/60Hz)
Power supply (50/60Hz)1 phase 100VAC±10%1 phase 200VAC±10%
Current consumption (A)(MAX)6.5/6.43.2/3.2
Starting current (A)15.6/14.77.5/7.1
Power consumption (W)(MAX)590/630600/610
Allowable ambient temperature (ºC)20 to 50
Allowable ambient humidity (%)10 to 85 (No condensation)
RefrigerantR-134a (A kind of freon that is not prohibited)
Temperature setting range (ºC)25 to 45
Number of fans2
OutputOutput of operation & alarm(250V 2A)
DisplayLED Temperature/Error RUN
Noise immunityLevel 4 in the fast transient/Burst immunity test
Noise (dB)Approx. 64/68
Vibration resistanceVibration frequency : 5Hz ; a double amplitude of 20mm
Paint colorMunsell 5Y7/1 Equivalent color of light beige
Outer dimensions (mm)H730×W300×D280
Weight(kg)26

ENC-AR1310LE

ModelENC-AR1310LE
TypeNon-drain Lateral-mount Type
Cooling schemeCompressor
Cooling capacity (W)1150/1300(50/60Hz)
Power supply (50/60Hz)1 phase 100VAC±10%
Current consumption (A)(MAX)8.6/9.0
Starting current (A)22.3/20.5
Power consumption (W)(MAX)770/870
Allowable ambient temperature (ºC)20 to 55
Allowable ambient humidity (%)10 to 85 (No condensation)
RefrigerantR-407c
Temperature setting range (ºC)25 to 45
Number of fans3
OutputOutput of operation & alarm(250V 2A)
DisplayLED Temperature/Error RUN
Noise immunityLevel 4 in the fast transient/Burst immunity test
Noise (dB)Approx. 68/72
Vibration resistanceVibration frequency : 5Hz ; a double amplitude of 20mm
Paint colorMunsell 5Y7/1 Equivalent color of light beige
Outer dimensions (mm)H900×W400×D251
Weight(kg)36

ENC-AR1320LE

ModelENC-AR1320LE
TypeNon-drain Lateral-mount Type
Cooling schemeCompressor
Cooling capacity (W)1150/1300 (50/60Hz)
Power supply (50/60Hz)1 phase 200V±10%
Current consumption (A)(MAX)4.2/4.4
Starting current (A)12.7/11.6
Power consumption (W)(MAX)805/880
Allowable ambient temperature (ºC)20 to 50
Allowable ambient humidity (%)10 to 85 (No condensation)
RefrigerantR-407c
Temperature setting range (ºC)25 to 45
Number of fans3
OutputOutput of operation & alarm(250V 2A)
DisplayLED Temperature/Error RUN
Paint colorMunsell 5Y7/1 Equivalent color of light beige
Outer dimensions (mm)H900×W400×D251
Weight(kg)36

ENC-AR2400LE

ModelENC-AR2400LE
TypeNon-drain Lateral-mount Type
Cooling schemeCompressor
Cooling capacity (W)2100/2400(50/60Hz)
Power supply (50/60Hz)3 phase 200VAC±10%
Current consumption (A)(MAX)5.0/4.6
Starting current (A)31/30
Power consumption (W)(MAX)1490/1770
Allowable ambient temperature (ºC)20 to 55
Allowable ambient humidity (%)10 to 85 (No condensation)
RefrigerantR-134a
Temperature setting range (ºC)25 to 45
Number of fans5
OutputOutput of operation & alarm(250V 2A)
DisplayLED Temperature/Error RUN
Noise immunityLevel 4 in the fast transient/Burst immunity test
Noise (dB)Approx. 70/73
Vibration resistanceVibration frequency : 5Hz ; a double amplitude of 20mm
Paint colorMunsell 5Y7/1 Equivalent color of light beige
Outer dimensions (mm)H1380×W450×D230
Weight(kg)63